Stopping and Starting the SPC Driver
The SPC driver must be running (in Configuration Mode or Started) to import the configuration files. If Configuration Mode is used, when engineering is complete the driver must be Started to establish a real connection to the field. You may also need to stop and restart the driver for certain settings, such as changes to alarm tables, to take effect.
- Desigo CC is configured to connect to an SPC intrusion system.
- System Manager is in Engineering mode.
- In System Browser select Management View.
- Depending on where the driver was created, select one of the following:
- Project > Management System > Servers > Main Server > Drivers > [SPC driver]
- Project > Management System > FEPs > [FEP station] > [drivers folder] > [SPC driver]. - In the Extended Operation tab, the Manager Status property indicates whether the driver is
Stopped,Started, or inConfiguration Mode. - If the driver is
Stopped, do one of the following:
- Click Start Conf… to start the driver without establishing a real field connection.
- Click Start to start the driver with a full connection to the field. - If the driver is running in
Configuration Mode, or if it isStartedbut you need to restart it:
a. Click Stop.
b. Click Start. - The Manager Status changes to
Started. The SPC driver is fully operational.